Features
- High accuracy, ± 0.5% ratio error, Phase shift error < 0.3%
- High linearity, large measurement range capacity (6000A or greater)
- High sensitivity, accuracy down to 50A
- Next Generation Design has less positional error
- High immunity to EMI and magnetic fields
- Ideal for use with WattsOn-Mark II Advanced Energy Meter
- Ideal for use with i-Spy Advanced 3-Phase AC Current Monitor
Product Description
The ULNRC-600 is a flexible, air-core current sensor which operates on the Rogowski Coil principle. The ULNRC-600 is designed and approved to be installed on insulated and/or bare conductors (bus bars).
The unique shielding system and precision windings minimize the positioning error and practically eliminate the influence of external magnetic fields.
The ULNRC-600 can be used directly with the WattsOn-Mark II Precision Energy Meters without an integrator or additional power supply. This offers accurate measurements in large power systems where conventional iron-core CTs may be hard to install.
Each ULNRC-600 coil has a unique serial number and is factory calibrated. Three identical coils are shipped with one meter for best accuracy.
The ULNRC-600 features UL Listing for easy retrofit in field applications.
Installation Advantages
Dimensions
All dimensions in mm
Specifications
| Input Range | 0.1A — 100,000A (AC) | ||
| Coil Length | 600 mm (23.6") | ||
| Inside Diameter | 190 mm (7.5") | ||
| Coil Thickness | 8.0 mm (0.32") | ||
| Output | 100mV/1000A (50Hz) 120mV/1000A (60Hz) | ||
| Output Waveform | AC mV (di/dt). Requires integrator for measurement of AC current (built into WattsOn-Mark II) | ||
| Outer Sheath | Thermoplastic UL94-V0 | ||
| Leads | Shielded pair AWG22, 15 m (49ft) AWM style 2586, 600V, 105°C X1 / X2 = Blue / White | ||
| Insulation Class | 1000V; 50-60 Hz, Cat III 600V; 50-60 Hz, Cat IV Pollution Degree 2 | ||
| Test Voltage | 7400 Vrms for 1 min | ||
| Certifications | UL Listed 61010-1 | ||
| Operating Temp | -40°C to 80°C | ||
| Ratio Error | 0.5 Class per IEC 61869-2 | ||
| Linearity | 0.2% | ||
| Positioning Error | With a 15 mm wire: One loop: < 1% of reading Two loops: < 0.3% of reading | ||
| Accuracy Range | Accuracy stated from 50A to 50kA | ||