Products

    All Products   

    Transducers

    Interfacing 


    Ordering
 
 

MSCT - Split Core Current Transformers (mA Output)


Applications in Elkor's Products:

  • Current Transformers for all ELKOR power transducers.
     

  • Current Transformers for the ETA3.x family of Current Transducers.
     

  • Current Transformers for i-Snail-X Current Sensors.


Specifications:

  MSCT1 MSCT2 MSCT3 MSCT6
Primary Wire Window 0.75"
(19mm)
1.25"
(32mm)
2.00"
(51mm)
3.00" x 5.00"
(76 x 127mm)
Maximum Continuous Current (Amps AC) 200A 600A 1500A 3000A
Output @ Max Input
(mA AC)
26.67mA 80mA 200mA 200mA
Insulation Class 600V; 50-60Hz
Leads AWG #22, 8’ (2.4m), CSA Type TEW, 600V, AWM Style 1015
Overload 1.5 x Max Input for 5 seconds
Max Open Circuit
Voltage
Output Clamped at 22V peak.

MSCT1

MSCT2

MSCT3

MSCT6

A

2.00"

3.25"

4.75"

5.80"

B

2.10"

3.35"

5.00"

7.50"

C

0.61"

1.00"

1.20"

1.20"

D

0.75"

1.25"

2.00"

3.00"

E

0.75"

1.25"

2.00"

5.00"
 

MSCT transformers sensors shall be installed on insulated conductors. 

Unlike the standard 5A CTs, the MSCT Current Transformers do not produce high voltage surge when opened . They generate a mV signal level and no special protection and/or shorting blocks are required. Maximum open secondary voltage is clamped at about 22 V peak.