MSCT - Split Core Current Transformers (mA Output)
-
Current Transformers for all ELKOR power
transducers.
-
Current Transformers for the ETA3.x family of
Current Transducers.
-
Current Transformers for i-Snail-X Current
Sensors.
|
|
| |
MSCT1 |
MSCT2 |
MSCT3 |
MSCT6 |
| Primary
Wire Window |
0.75"
(19mm) |
1.25"
(32mm) |
2.00"
(51mm) |
3.00" x 5.00"
(76 x 127mm) |
| Maximum
Continuous Current (Amps AC) |
200A |
600A |
1500A |
3000A |
Output @
Max Input
(mA AC) |
26.67mA |
80mA |
200mA |
200mA |
| Insulation
Class |
600V;
50-60Hz |
| Leads |
AWG #22, 8’
(2.4m), CSA Type TEW, 600V, AWM Style 1015 |
| Overload |
1.5 x Max
Input for 5 seconds |
Max Open
Circuit
Voltage |
Output
Clamped at 22V peak. |
|
|
MSCT1 |
MSCT2 |
MSCT3 |
MSCT6 |
|
A |
2.00" |
3.25" |
4.75" |
5.80" |
|
B |
2.10" |
3.35" |
5.00" |
7.50" |
|
C |
0.61" |
1.00" |
1.20" |
1.20" |
|
D |
0.75" |
1.25" |
2.00" |
3.00" |
|
E |
0.75" |
1.25" |
2.00" |
5.00" |
|
 |
|
MSCT transformers sensors shall
be installed on insulated conductors.
Unlike the standard 5A CTs, the MSCT Current
Transformers do not produce high voltage surge when opened . They
generate a mV signal level and no special protection and/or shorting
blocks are required. Maximum open secondary voltage is clamped at
about 22 V peak.
|

MSCTx
Datasheet |
PDF |
copyright (c) Elkor Technologies Inc.
|